ConduitCount

How many #3 THHN fit in 1" Rigid?

33 AWG THHN/THWN-2 wires in 1" Rigid metal conduit (RMC, GRC)

0.887 sq in × 40 % = 0.3548 sq in allowed. ÷ 0.0973 sq in per wire = 3.65, so 3.

3 #3 THHN in 1" Rigid, drawn to scale

This pull in numbers

3 wires fill
32.9 % of 1" Rigid
Limit for three or more
40 %
For 4 or more
1-1/4" Rigid, up to 6
Pipe to wire diameter
3.02 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 3.02 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.

Before you pull 3

#3 THHN in other 1" conduit

#3 THHN in other Rigid sizes

Other wire sizes in 1" Rigid

Charts