ConduitCount

How many #3/0 THHN fit in 1" PVC Sch 40?

13/0 AWG THHN/THWN-2 wires in 1" Rigid PVC conduit, Schedule 40

0.832 sq in × 53 % = 0.4410 sq in allowed. ÷ 0.2679 sq in per wire = 1.65.

1 #3/0 THHN in 1" PVC Sch 40, drawn to scale

This pull in numbers

1 wires fill
32.2 % of 1" PVC Sch 40
Limit for one
53 %
For 2 or more
1-1/2" PVC Sch 40, up to 3
Pipe to wire diameter
1.76 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

#3/0 THHN in other 1" conduit

#3/0 THHN in other PVC Sch 40 sizes

Other wire sizes in 1" PVC Sch 40

Charts