63 AWG THHN/THWN-2 wires in 1-1/4" Rigid PVC conduit, Schedule 40

1.453 sq in × 40 % = 0.5812 sq in allowed. ÷ 0.0973 sq in per wire = 5.97, which Note 7 rounds up to 6 because the decimal is 0.8 or more.

6 #3 THHN in 1-1/4" PVC Sch 40, drawn to scale

This pull in numbers

6 wires fill
40.2 % of 1-1/4" PVC Sch 40
Limit for three or more
40 %
For 7 or more
1-1/2" PVC Sch 40, up to 8
Pipe to wire diameter
3.86 to 1
In THW insulation
5 fit
In XHHW-2 insulation
6 fit

Before you pull 6

#3 THHN in other 1-1/4" conduit

#3 THHN in other PVC Sch 40 sizes

Other wire sizes in 1-1/4" PVC Sch 40