How many #14 THHN fit in 1" PVC Sch 40?

3414 AWG THHN/THWN-2 wires in 1" Rigid PVC conduit, Schedule 40

0.832 sq in × 40 % = 0.3328 sq in allowed. ÷ 0.0097 sq in per wire = 34.31, so 34.

34 #14 THHN in 1" PVC Sch 40, drawn to scale

This pull in numbers

34 wires fill
39.6 % of 1" PVC Sch 40
Limit for three or more
40 %
For 35 or more
1-1/4" PVC Sch 40, up to 60
Pipe to wire diameter
9.27 to 1
In THW insulation
24 fit
In XHHW-2 insulation
24 fit

Before you pull 34

#14 THHN in other 1" conduit

#14 THHN in other PVC Sch 40 sizes

Other wire sizes in 1" PVC Sch 40

Charts