ConduitCount

How many #3 THHN fit in 1-1/2" Rigid?

83 AWG THHN/THWN-2 wires in 1-1/2" Rigid metal conduit (RMC, GRC)

2.071 sq in × 40 % = 0.8284 sq in allowed. ÷ 0.0973 sq in per wire = 8.51, so 8.

8 #3 THHN in 1-1/2" Rigid, drawn to scale

This pull in numbers

8 wires fill
37.6 % of 1-1/2" Rigid
Limit for three or more
40 %
For 9 or more
2" Rigid, up to 14
Pipe to wire diameter
4.61 to 1
In THW insulation
7 fit
In XHHW-2 insulation
8 fit

Before you pull 8

#3 THHN in other 1-1/2" conduit

#3 THHN in other Rigid sizes

Other wire sizes in 1-1/2" Rigid

Charts