How many #3 THHN fit in 1-1/4" Rigid?

63 AWG THHN/THWN-2 wires in 1-1/4" Rigid metal conduit (RMC, GRC)

1.526 sq in × 40 % = 0.6104 sq in allowed. ÷ 0.0973 sq in per wire = 6.27, so 6.

6 #3 THHN in 1-1/4" Rigid, drawn to scale

This pull in numbers

6 wires fill
38.3 % of 1-1/4" Rigid
Limit for three or more
40 %
For 7 or more
1-1/2" Rigid, up to 8
Pipe to wire diameter
3.96 to 1
In THW insulation
5 fit
In XHHW-2 insulation
6 fit

Before you pull 6

#3 THHN in other 1-1/4" conduit

#3 THHN in other Rigid sizes

Other wire sizes in 1-1/4" Rigid