ConduitCount

How many #3 THHN fit in 4" Rigid?

533 AWG THHN/THWN-2 wires in 4" Rigid metal conduit (RMC, GRC)

12.882 sq in × 40 % = 5.1528 sq in allowed. ÷ 0.0973 sq in per wire = 52.96, which Note 7 rounds up to 53 because the decimal is 0.8 or more.

53 #3 THHN in 4" Rigid, drawn to scale

This pull in numbers

53 wires fill
40.0 % of 4" Rigid
Limit for three or more
40 %
For 54 or more
5" Rigid, up to 83
Pipe to wire diameter
11.51 to 1
In THW insulation
45 fit
In XHHW-2 insulation
53 fit

Before you pull 53

#3 THHN in other 4" conduit

#3 THHN in other Rigid sizes

Other wire sizes in 4" Rigid

Charts