ConduitCount

How many 300 kcmil THHN fit in 3" EMT?

7300 kcmil THHN/THWN-2 wires in 3" Electrical metallic tubing

8.846 sq in × 40 % = 3.5384 sq in allowed. ÷ 0.4608 sq in per wire = 7.68, so 7.

7 300 kcmil THHN in 3" EMT, drawn to scale

This pull in numbers

7 wires fill
36.5 % of 3" EMT
Limit for three or more
40 %
For 8 or more
3-1/2" EMT, up to 10
Pipe to wire diameter
4.38 to 1
In THW insulation
6 fit
In XHHW-2 insulation
8 fit

Before you pull 7

300 kcmil THHN in other 3" conduit

300 kcmil THHN in other EMT sizes

Other wire sizes in 3" EMT

Charts