ConduitCount

How many #1/0 THHN fit in 3" EMT?

191/0 AWG THHN/THWN-2 wires in 3" Electrical metallic tubing

8.846 sq in × 40 % = 3.5384 sq in allowed. ÷ 0.1855 sq in per wire = 19.07, so 19.

19 #1/0 THHN in 3" EMT, drawn to scale

This pull in numbers

19 wires fill
39.8 % of 3" EMT
Limit for three or more
40 %
For 20 or more
3-1/2" EMT, up to 25
Pipe to wire diameter
6.91 to 1
In THW insulation
16 fit
In XHHW-2 insulation
19 fit

Before you pull 19

#1/0 THHN in other 3" conduit

#1/0 THHN in other EMT sizes

Other wire sizes in 3" EMT

Charts