How many 300 kcmil THHN fit in 3-1/2" EMT?

10300 kcmil THHN/THWN-2 wires in 3-1/2" Electrical metallic tubing

11.545 sq in × 40 % = 4.6180 sq in allowed. ÷ 0.4608 sq in per wire = 10.02, so 10.

10 300 kcmil THHN in 3-1/2" EMT, drawn to scale

This pull in numbers

10 wires fill
39.9 % of 3-1/2" EMT
Limit for three or more
40 %
For 11 or more
4" EMT, up to 13
Pipe to wire diameter
5.01 to 1
In THW insulation
8 fit
In XHHW-2 insulation
10 fit

Before you pull 10

300 kcmil THHN in other 3-1/2" conduit

300 kcmil THHN in other EMT sizes

Other wire sizes in 3-1/2" EMT