ConduitCount

How many 300 kcmil THHN fit in 3" IMC?

7300 kcmil THHN/THWN-2 wires in 3" Intermediate metal conduit

7.922 sq in × 40 % = 3.1688 sq in allowed. ÷ 0.4608 sq in per wire = 6.88, which Note 7 rounds up to 7 because the decimal is 0.8 or more.

7 300 kcmil THHN in 3" IMC, drawn to scale

This pull in numbers

7 wires fill
40.7 % of 3" IMC
Limit for three or more
40 %
For 8 or more
3-1/2" IMC, up to 9
Pipe to wire diameter
4.15 to 1
In THW insulation
6 fit
In XHHW-2 insulation
7 fit

Before you pull 7

300 kcmil THHN in other 3" conduit

300 kcmil THHN in other IMC sizes

Other wire sizes in 3" IMC

Charts