3300 kcmil THHN/THWN-2 wires in 2" Electrical metallic tubing

3.356 sq in × 40 % = 1.3424 sq in allowed. ÷ 0.4608 sq in per wire = 2.91, which Note 7 rounds up to 3 because the decimal is 0.8 or more.

3 300 kcmil THHN in 2" EMT, drawn to scale

This pull in numbers

3 wires fill
41.2 % of 2" EMT
Limit for three or more
40 %
For 4 or more
2-1/2" EMT, up to 5
Pipe to wire diameter
2.70 to 1
In THW insulation
1 fit
In XHHW-2 insulation
3 fit