ConduitCount

How many 300 kcmil THHN fit in 4" Flex?

11300 kcmil THHN/THWN-2 wires in 4" Flexible metal conduit (FMC, Greenfield)

12.566 sq in × 40 % = 5.0264 sq in allowed. ÷ 0.4608 sq in per wire = 10.91, which Note 7 rounds up to 11 because the decimal is 0.8 or more.

11 300 kcmil THHN in 4" Flex, drawn to scale

This pull in numbers

11 wires fill
40.3 % of 4" Flex
Limit for three or more
40 %
For 12 or more
no bigger Flex
Pipe to wire diameter
5.22 to 1
In THW insulation
9 fit
In XHHW-2 insulation
11 fit

Before you pull 11

300 kcmil THHN in other 4" conduit

ConduitInside areaMost 300 kcmil THHN
Electrical metallic tubing14.75313
Intermediate metal conduit13.63112
Rigid metal conduit (RMC, GRC)12.88211
Rigid PVC conduit, Schedule 4012.55411
Rigid PVC conduit, Schedule 8011.2589
Flexible metal conduit (FMC, Greenfield)12.56611
Liquidtight flexible metal conduit (LFMC)12.69211

300 kcmil THHN in other Flex sizes

Other wire sizes in 4" Flex

Charts