How many 300 kcmil THHN fit in 4" Rigid?

11300 kcmil THHN/THWN-2 wires in 4" Rigid metal conduit (RMC, GRC)

12.882 sq in × 40 % = 5.1528 sq in allowed. ÷ 0.4608 sq in per wire = 11.18, so 11.

11 300 kcmil THHN in 4" Rigid, drawn to scale

This pull in numbers

11 wires fill
39.3 % of 4" Rigid
Limit for three or more
40 %
For 12 or more
5" Rigid, up to 17
Pipe to wire diameter
5.29 to 1
In THW insulation
9 fit
In XHHW-2 insulation
11 fit