ConduitCount

How many 300 kcmil THHN fit in 4" PVC Sch 40?

11300 kcmil THHN/THWN-2 wires in 4" Rigid PVC conduit, Schedule 40

12.554 sq in × 40 % = 5.0216 sq in allowed. ÷ 0.4608 sq in per wire = 10.90, which Note 7 rounds up to 11 because the decimal is 0.8 or more.

11 300 kcmil THHN in 4" PVC Sch 40, drawn to scale

This pull in numbers

11 wires fill
40.4 % of 4" PVC Sch 40
Limit for three or more
40 %
For 12 or more
5" PVC Sch 40, up to 17
Pipe to wire diameter
5.22 to 1
In THW insulation
9 fit
In XHHW-2 insulation
11 fit

Before you pull 11

300 kcmil THHN in other 4" conduit

300 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 4" PVC Sch 40

Charts