ConduitCount

How many 300 kcmil THHN fit in 4" IMC?

12300 kcmil THHN/THWN-2 wires in 4" Intermediate metal conduit

13.631 sq in × 40 % = 5.4524 sq in allowed. ÷ 0.4608 sq in per wire = 11.83, which Note 7 rounds up to 12 because the decimal is 0.8 or more.

12 300 kcmil THHN in 4" IMC, drawn to scale

This pull in numbers

12 wires fill
40.6 % of 4" IMC
Limit for three or more
40 %
For 13 or more
no bigger IMC
Pipe to wire diameter
5.44 to 1
In THW insulation
10 fit
In XHHW-2 insulation
12 fit

Before you pull 12

300 kcmil THHN in other 4" conduit

300 kcmil THHN in other IMC sizes

Other wire sizes in 4" IMC

Charts