ConduitCount

How many 300 kcmil THHN fit in 5" PVC Sch 80?

15300 kcmil THHN/THWN-2 wires in 5" Rigid PVC conduit, Schedule 80

17.855 sq in × 40 % = 7.1420 sq in allowed. ÷ 0.4608 sq in per wire = 15.50, so 15.

15 300 kcmil THHN in 5" PVC Sch 80, drawn to scale

This pull in numbers

15 wires fill
38.7 % of 5" PVC Sch 80
Limit for three or more
40 %
For 16 or more
6" PVC Sch 80, up to 22
Pipe to wire diameter
6.22 to 1
In THW insulation
13 fit
In XHHW-2 insulation
15 fit

Before you pull 15

300 kcmil THHN in other 5" conduit

ConduitInside areaMost 300 kcmil THHN
Rigid metal conduit (RMC, GRC)20.21217
Rigid PVC conduit, Schedule 4019.76117
Rigid PVC conduit, Schedule 8017.85515

300 kcmil THHN in other PVC Sch 80 sizes

Other wire sizes in 5" PVC Sch 80

Charts