ConduitCount

How many #2/0 THHN fit in 5" PVC Sch 80?

322/0 AWG THHN/THWN-2 wires in 5" Rigid PVC conduit, Schedule 80

17.855 sq in × 40 % = 7.1420 sq in allowed. ÷ 0.2223 sq in per wire = 32.13, so 32.

32 #2/0 THHN in 5" PVC Sch 80, drawn to scale

This pull in numbers

32 wires fill
39.8 % of 5" PVC Sch 80
Limit for three or more
40 %
For 33 or more
6" PVC Sch 80, up to 46
Pipe to wire diameter
8.96 to 1
In THW insulation
27 fit
In XHHW-2 insulation
32 fit

Before you pull 32

#2/0 THHN in other 5" conduit

ConduitInside areaMost #2/0 THHN
Rigid metal conduit (RMC, GRC)20.21236
Rigid PVC conduit, Schedule 4019.76135
Rigid PVC conduit, Schedule 8017.85532

#2/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 5" PVC Sch 80

Charts