ConduitCount

How many #4 THHN fit in 5" PVC Sch 80?

864 AWG THHN/THWN-2 wires in 5" Rigid PVC conduit, Schedule 80

17.855 sq in × 40 % = 7.1420 sq in allowed. ÷ 0.0824 sq in per wire = 86.67, so 86.

86 #4 THHN in 5" PVC Sch 80, drawn to scale

This pull in numbers

86 wires fill
39.7 % of 5" PVC Sch 80
Limit for three or more
40 %
For 87 or more
6" PVC Sch 80, up to 124
Pipe to wire diameter
14.72 to 1
In THW insulation
73 fit
In XHHW-2 insulation
87 fit

Before you pull 86

#4 THHN in other 5" conduit

ConduitInside areaMost #4 THHN
Rigid metal conduit (RMC, GRC)20.21298
Rigid PVC conduit, Schedule 4019.76196
Rigid PVC conduit, Schedule 8017.85586

#4 THHN in other PVC Sch 80 sizes

Other wire sizes in 5" PVC Sch 80

Charts