ConduitCount

How many #3/0 THHN fit in 5" PVC Sch 80?

263/0 AWG THHN/THWN-2 wires in 5" Rigid PVC conduit, Schedule 80

17.855 sq in × 40 % = 7.1420 sq in allowed. ÷ 0.2679 sq in per wire = 26.66, so 26.

26 #3/0 THHN in 5" PVC Sch 80, drawn to scale

This pull in numbers

26 wires fill
39.0 % of 5" PVC Sch 80
Limit for three or more
40 %
For 27 or more
6" PVC Sch 80, up to 38
Pipe to wire diameter
8.16 to 1
In THW insulation
23 fit
In XHHW-2 insulation
27 fit

Before you pull 26

#3/0 THHN in other 5" conduit

ConduitInside areaMost #3/0 THHN
Rigid metal conduit (RMC, GRC)20.21230
Rigid PVC conduit, Schedule 4019.76129
Rigid PVC conduit, Schedule 8017.85526

#3/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 5" PVC Sch 80

Charts