ConduitCount

How many #2 THHN fit in 5" PVC Sch 80?

612 AWG THHN/THWN-2 wires in 5" Rigid PVC conduit, Schedule 80

17.855 sq in × 40 % = 7.1420 sq in allowed. ÷ 0.1158 sq in per wire = 61.68, so 61.

61 #2 THHN in 5" PVC Sch 80, drawn to scale

This pull in numbers

61 wires fill
39.6 % of 5" PVC Sch 80
Limit for three or more
40 %
For 62 or more
6" PVC Sch 80, up to 88
Pipe to wire diameter
12.42 to 1
In THW insulation
53 fit
In XHHW-2 insulation
62 fit

Before you pull 61

#2 THHN in other 5" conduit

ConduitInside areaMost #2 THHN
Rigid metal conduit (RMC, GRC)20.21270
Rigid PVC conduit, Schedule 4019.76168
Rigid PVC conduit, Schedule 8017.85561

#2 THHN in other PVC Sch 80 sizes

Other wire sizes in 5" PVC Sch 80