ConduitCount

How many #6 THHN fit in 5" PVC Sch 80?

1416 AWG THHN/THWN-2 wires in 5" Rigid PVC conduit, Schedule 80

17.855 sq in × 40 % = 7.1420 sq in allowed. ÷ 0.0507 sq in per wire = 140.87, which Note 7 rounds up to 141 because the decimal is 0.8 or more.

141 #6 THHN in 5" PVC Sch 80, drawn to scale

This pull in numbers

141 wires fill
40.0 % of 5" PVC Sch 80
Limit for three or more
40 %
For 142 or more
6" PVC Sch 80, up to 202
Pipe to wire diameter
18.77 to 1
In THW insulation
98 fit
In XHHW-2 insulation
121 fit

Before you pull 141

#6 THHN in other 5" conduit

ConduitInside areaMost #6 THHN
Rigid metal conduit (RMC, GRC)20.212159
Rigid PVC conduit, Schedule 4019.761156
Rigid PVC conduit, Schedule 8017.855141

#6 THHN in other PVC Sch 80 sizes

Other wire sizes in 5" PVC Sch 80

Charts