How many 350 kcmil THHN fit in 1-1/2" PVC Sch 40?
1350 kcmil THHN/THWN-2 wires in 1-1/2" Rigid PVC conduit, Schedule 40
1.986 sq in × 53 % = 1.0526 sq in allowed. ÷ 0.5242 sq in per wire = 2.01.
This pull in numbers
- 1 wires fill
- 26.4 % of 1-1/2" PVC Sch 40
- Limit for one
- 53 %
- For 2 or more
- 2-1/2" PVC Sch 40, up to 3
- Pipe to wire diameter
- 1.95 to 1
- In THW insulation
- 1 fit
- In XHHW-2 insulation
- 1 fit
Before you pull 1
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 1 is the total, not the hots.
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
350 kcmil THHN in other 1-1/2" conduit
| Conduit | Inside area | Most 350 kcmil THHN |
|---|---|---|
| Electrical metallic tubing | 2.036 | 1 |
| Intermediate metal conduit | 2.225 | 1 |
| Rigid metal conduit (RMC, GRC) | 2.071 | 1 |
| Rigid PVC conduit, Schedule 40 | 1.986 | 1 |
| Rigid PVC conduit, Schedule 80 | 1.711 | 1 |
| Flexible metal conduit (FMC, Greenfield) | 1.858 | 1 |
| Liquidtight flexible metal conduit (LFMC) | 1.981 | 1 |
| Electrical nonmetallic tubing (smurf tube) | 1.986 | 1 |
350 kcmil THHN in other PVC Sch 40 sizes
Other wire sizes in 1-1/2" PVC Sch 40
#14: 82#12: 59#10: 37#8: 21#6: 15#4: 9#3: 8#2: 7#1: 5#1/0: 4#2/0: 3#3/0: 3#4/0: 1250 kcmil: 1300 kcmil: 1350 kcmil: 1500 kcmil: 1