ConduitCount

How many #3/0 THHN fit in 1-1/2" PVC Sch 40?

33/0 AWG THHN/THWN-2 wires in 1-1/2" Rigid PVC conduit, Schedule 40

1.986 sq in × 40 % = 0.7944 sq in allowed. ÷ 0.2679 sq in per wire = 2.97, which Note 7 rounds up to 3 because the decimal is 0.8 or more.

3 #3/0 THHN in 1-1/2" PVC Sch 40, drawn to scale

This pull in numbers

3 wires fill
40.5 % of 1-1/2" PVC Sch 40
Limit for three or more
40 %
For 4 or more
2" PVC Sch 40, up to 5
Pipe to wire diameter
2.72 to 1
In THW insulation
1 fit
In XHHW-2 insulation
3 fit

Before you pull 3

#3/0 THHN in other 1-1/2" conduit

#3/0 THHN in other PVC Sch 40 sizes

Other wire sizes in 1-1/2" PVC Sch 40

Charts