ConduitCount

How many #4 THHN fit in 1-1/2" PVC Sch 40?

94 AWG THHN/THWN-2 wires in 1-1/2" Rigid PVC conduit, Schedule 40

1.986 sq in × 40 % = 0.7944 sq in allowed. ÷ 0.0824 sq in per wire = 9.64, so 9.

9 #4 THHN in 1-1/2" PVC Sch 40, drawn to scale

This pull in numbers

9 wires fill
37.3 % of 1-1/2" PVC Sch 40
Limit for three or more
40 %
For 10 or more
2" PVC Sch 40, up to 16
Pipe to wire diameter
4.91 to 1
In THW insulation
8 fit
In XHHW-2 insulation
9 fit

Before you pull 9

#4 THHN in other 1-1/2" conduit

#4 THHN in other PVC Sch 40 sizes

Other wire sizes in 1-1/2" PVC Sch 40

Charts