ConduitCount

1-1/2" PVC Sch 40 conduit fill

1-1/2" Rigid PVC conduit, Schedule 40 has an inside area of 1.986 sq in (1.590 in across). Three or more wires may take 40 % of it: 0.7944 sq in.

One wire, 53 %
1.0526 sq in
Two wires, 31 %
0.6157 sq in
Three or more, 40 %
0.7944 sq in
Nipple, 60 %
1.1916 sq in
Support
Every 5 ft, 3 ft from boxes
Sold in
10 ft sticks
59 #12 THHN, the most it may hold, drawn to scale

How many wires fit in 1-1/2" PVC Sch 40

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG825757
12 AWG594444
10 AWG373232
8 AWG211818
6 AWG151311
4 AWG998
3 AWG887
2 AWG776
1 AWG554
1/0 AWG443
2/0 AWG333
3/0 AWG331
4/0 AWG111
250 kcmil111
300 kcmil111
350 kcmil111
400 kcmil111
500 kcmil111
600 kcmil111
700 kcmil110
750 kcmil100

Other 1-1/2" conduit

ConduitInside area#14#12#10#8#6
Rigid PVC conduit, Schedule 401.9868259372115
Electrical metallic tubing2.0368461382216
Intermediate metal conduit2.2259167422417
Rigid metal conduit (RMC, GRC)2.0718562392216
Rigid PVC conduit, Schedule 801.7117051321813
Flexible metal conduit (FMC, Greenfield)1.8587656352014
Liquidtight flexible metal conduit (LFMC)1.9818159372115
Electrical nonmetallic tubing (smurf tube)1.9868259372115

About PVC Sch 40

Schedule 40 is the standard PVC wall. Support spacing gets wider as the size goes up (Table 352.30), and long runs in the sun need expansion fittings (352.44). See strap spacing and the fill rules.