ConduitCount

How many 350 kcmil THHN fit in 1-1/2" IMC?

1350 kcmil THHN/THWN-2 wires in 1-1/2" Intermediate metal conduit

2.225 sq in × 53 % = 1.1793 sq in allowed. ÷ 0.5242 sq in per wire = 2.25.

1 350 kcmil THHN in 1-1/2" IMC, drawn to scale

This pull in numbers

1 wires fill
23.6 % of 1-1/2" IMC
Limit for one
53 %
For 2 or more
2" IMC, up to 2
Pipe to wire diameter
2.06 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

350 kcmil THHN in other 1-1/2" conduit

350 kcmil THHN in other IMC sizes

Other wire sizes in 1-1/2" IMC

Charts