ConduitCount

How many 350 kcmil THHN fit in 6" PVC Sch 40?

21350 kcmil THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 40

28.567 sq in × 40 % = 11.4268 sq in allowed. ÷ 0.5242 sq in per wire = 21.80, so 21.

21 350 kcmil THHN in 6" PVC Sch 40, drawn to scale

This pull in numbers

21 wires fill
38.5 % of 6" PVC Sch 40
Limit for three or more
40 %
For 22 or more
no bigger PVC Sch 40
Pipe to wire diameter
7.38 to 1
In THW insulation
19 fit
In XHHW-2 insulation
22 fit

Before you pull 21

350 kcmil THHN in other 6" conduit

ConduitInside areaMost 350 kcmil THHN
Rigid metal conduit (RMC, GRC)29.15822
Rigid PVC conduit, Schedule 4028.56721
Rigid PVC conduit, Schedule 8025.59819

350 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 6" PVC Sch 40

Charts