ConduitCount

How many 250 kcmil THHN fit in 1-1/2" PVC Sch 40?

1250 kcmil THHN/THWN-2 wires in 1-1/2" Rigid PVC conduit, Schedule 40

1.986 sq in × 53 % = 1.0526 sq in allowed. ÷ 0.3970 sq in per wire = 2.65.

1 250 kcmil THHN in 1-1/2" PVC Sch 40, drawn to scale

This pull in numbers

1 wires fill
20.0 % of 1-1/2" PVC Sch 40
Limit for one
53 %
For 2 or more
2" PVC Sch 40, up to 3
Pipe to wire diameter
2.24 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

250 kcmil THHN in other 1-1/2" conduit

250 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 1-1/2" PVC Sch 40

Charts