ConduitCount

How many #4 THHN fit in 1-1/2" EMT?

104 AWG THHN/THWN-2 wires in 1-1/2" Electrical metallic tubing

2.036 sq in × 40 % = 0.8144 sq in allowed. ÷ 0.0824 sq in per wire = 9.88, which Note 7 rounds up to 10 because the decimal is 0.8 or more.

10 #4 THHN in 1-1/2" EMT, drawn to scale

This pull in numbers

10 wires fill
40.5 % of 1-1/2" EMT
Limit for three or more
40 %
For 11 or more
2" EMT, up to 16
Pipe to wire diameter
4.97 to 1
In THW insulation
8 fit
In XHHW-2 insulation
10 fit

Before you pull 10

#4 THHN in other 1-1/2" conduit

#4 THHN in other EMT sizes

Other wire sizes in 1-1/2" EMT

Charts