ConduitCount

How many #4 THHN fit in 1-1/4" EMT?

74 AWG THHN/THWN-2 wires in 1-1/4" Electrical metallic tubing

1.496 sq in × 40 % = 0.5984 sq in allowed. ÷ 0.0824 sq in per wire = 7.26, so 7.

7 #4 THHN in 1-1/4" EMT, drawn to scale

This pull in numbers

7 wires fill
38.6 % of 1-1/4" EMT
Limit for three or more
40 %
For 8 or more
1-1/2" EMT, up to 10
Pipe to wire diameter
4.26 to 1
In THW insulation
6 fit
In XHHW-2 insulation
7 fit

Before you pull 7

#4 THHN in other 1-1/4" conduit

#4 THHN in other EMT sizes

Other wire sizes in 1-1/4" EMT

Charts