ConduitCount

How many 500 kcmil THHN fit in 2-1/2" EMT?

3500 kcmil THHN/THWN-2 wires in 2-1/2" Electrical metallic tubing

5.858 sq in × 40 % = 2.3432 sq in allowed. ÷ 0.7073 sq in per wire = 3.31, so 3.

3 500 kcmil THHN in 2-1/2" EMT, drawn to scale

This pull in numbers

3 wires fill
36.2 % of 2-1/2" EMT
Limit for three or more
40 %
For 4 or more
3" EMT, up to 5
Pipe to wire diameter
2.88 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 2.88 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.

Before you pull 3

500 kcmil THHN in other 2-1/2" conduit

500 kcmil THHN in other EMT sizes

Other wire sizes in 2-1/2" EMT

Charts