ConduitCount

How many #6 THHN fit in 2-1/2" EMT?

466 AWG THHN/THWN-2 wires in 2-1/2" Electrical metallic tubing

5.858 sq in × 40 % = 2.3432 sq in allowed. ÷ 0.0507 sq in per wire = 46.22, so 46.

46 #6 THHN in 2-1/2" EMT, drawn to scale

This pull in numbers

46 wires fill
39.8 % of 2-1/2" EMT
Limit for three or more
40 %
For 47 or more
3" EMT, up to 69
Pipe to wire diameter
10.75 to 1
In THW insulation
32 fit
In XHHW-2 insulation
39 fit

Before you pull 46

#6 THHN in other 2-1/2" conduit

#6 THHN in other EMT sizes

Other wire sizes in 2-1/2" EMT

Charts