ConduitCount

How many #1/0 THHN fit in 2-1/2" EMT?

121/0 AWG THHN/THWN-2 wires in 2-1/2" Electrical metallic tubing

5.858 sq in × 40 % = 2.3432 sq in allowed. ÷ 0.1855 sq in per wire = 12.63, so 12.

12 #1/0 THHN in 2-1/2" EMT, drawn to scale

This pull in numbers

12 wires fill
38.0 % of 2-1/2" EMT
Limit for three or more
40 %
For 13 or more
3" EMT, up to 19
Pipe to wire diameter
5.62 to 1
In THW insulation
10 fit
In XHHW-2 insulation
13 fit

Before you pull 12

#1/0 THHN in other 2-1/2" conduit

#1/0 THHN in other EMT sizes

Other wire sizes in 2-1/2" EMT

Charts