How many 500 kcmil THHN fit in 2-1/2" IMC?

3500 kcmil THHN/THWN-2 wires in 2-1/2" Intermediate metal conduit

5.135 sq in × 40 % = 2.0540 sq in allowed. ÷ 0.7073 sq in per wire = 2.90, which Note 7 rounds up to 3 because the decimal is 0.8 or more.

3 500 kcmil THHN in 2-1/2" IMC, drawn to scale

This pull in numbers

3 wires fill
41.3 % of 2-1/2" IMC
Limit for three or more
40 %
For 4 or more
3" IMC, up to 4
Pipe to wire diameter
2.69 to 1
In THW insulation
2 fit
In XHHW-2 insulation
3 fit

Before you pull 3

500 kcmil THHN in other 2-1/2" conduit

500 kcmil THHN in other IMC sizes

Other wire sizes in 2-1/2" IMC