ConduitCount

How many #2/0 THHN fit in 2-1/2" EMT?

102/0 AWG THHN/THWN-2 wires in 2-1/2" Electrical metallic tubing

5.858 sq in × 40 % = 2.3432 sq in allowed. ÷ 0.2223 sq in per wire = 10.54, so 10.

10 #2/0 THHN in 2-1/2" EMT, drawn to scale

This pull in numbers

10 wires fill
37.9 % of 2-1/2" EMT
Limit for three or more
40 %
For 11 or more
3" EMT, up to 16
Pipe to wire diameter
5.13 to 1
In THW insulation
9 fit
In XHHW-2 insulation
10 fit

Before you pull 10

#2/0 THHN in other 2-1/2" conduit

#2/0 THHN in other EMT sizes

Other wire sizes in 2-1/2" EMT