How many 500 kcmil THHN fit in 5" Rigid?
11500 kcmil THHN/THWN-2 wires in 5" Rigid metal conduit (RMC, GRC)
20.212 sq in × 40 % = 8.0848 sq in allowed. ÷ 0.7073 sq in per wire = 11.43, so 11.
This pull in numbers
- 11 wires fill
- 38.5 % of 5" Rigid
- Limit for three or more
- 40 %
- For 12 or more
- 6" Rigid, up to 16
- Pipe to wire diameter
- 5.35 to 1
- In THW insulation
- 10 fit
- In XHHW-2 insulation
- 11 fit
Before you pull 11
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 11 is the total, not the hots.
- Derating. If all 11 were current-carrying, each would be adjusted to 50 % of its ampacity (Table 310.15(C)(1)): a 500 kcmil THHN at 430 A in the 90 °C column becomes 215 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
500 kcmil THHN in other 5" conduit
| Conduit | Inside area | Most 500 kcmil THHN |
|---|---|---|
| Rigid metal conduit (RMC, GRC) | 20.212 | 11 |
| Rigid PVC conduit, Schedule 40 | 19.761 | 11 |
| Rigid PVC conduit, Schedule 80 | 17.855 | 10 |
500 kcmil THHN in other Rigid sizes
Other wire sizes in 5" Rigid
#6: 159#4: 98#3: 83#2: 70#1: 51#1/0: 43#2/0: 36#3/0: 30#4/0: 25250 kcmil: 20300 kcmil: 17350 kcmil: 15500 kcmil: 11