ConduitCount

How many #1/0 THHN fit in 5" Rigid?

431/0 AWG THHN/THWN-2 wires in 5" Rigid metal conduit (RMC, GRC)

20.212 sq in × 40 % = 8.0848 sq in allowed. ÷ 0.1855 sq in per wire = 43.58, so 43.

43 #1/0 THHN in 5" Rigid, drawn to scale

This pull in numbers

43 wires fill
39.5 % of 5" Rigid
Limit for three or more
40 %
For 44 or more
6" Rigid, up to 63
Pipe to wire diameter
10.44 to 1
In THW insulation
36 fit
In XHHW-2 insulation
44 fit

Before you pull 43

#1/0 THHN in other 5" conduit

ConduitInside areaMost #1/0 THHN
Rigid metal conduit (RMC, GRC)20.21243
Rigid PVC conduit, Schedule 4019.76142
Rigid PVC conduit, Schedule 8017.85538

#1/0 THHN in other Rigid sizes

Other wire sizes in 5" Rigid

Charts