ConduitCount

How many #2/0 THHN fit in 5" Rigid?

362/0 AWG THHN/THWN-2 wires in 5" Rigid metal conduit (RMC, GRC)

20.212 sq in × 40 % = 8.0848 sq in allowed. ÷ 0.2223 sq in per wire = 36.37, so 36.

36 #2/0 THHN in 5" Rigid, drawn to scale

This pull in numbers

36 wires fill
39.6 % of 5" Rigid
Limit for three or more
40 %
For 37 or more
6" Rigid, up to 52
Pipe to wire diameter
9.54 to 1
In THW insulation
31 fit
In XHHW-2 insulation
37 fit

Before you pull 36

#2/0 THHN in other 5" conduit

ConduitInside areaMost #2/0 THHN
Rigid metal conduit (RMC, GRC)20.21236
Rigid PVC conduit, Schedule 4019.76135
Rigid PVC conduit, Schedule 8017.85532

#2/0 THHN in other Rigid sizes

Other wire sizes in 5" Rigid

Charts