ConduitCount

How many #6 THHN fit in 5" Rigid?

1596 AWG THHN/THWN-2 wires in 5" Rigid metal conduit (RMC, GRC)

20.212 sq in × 40 % = 8.0848 sq in allowed. ÷ 0.0507 sq in per wire = 159.46, so 159.

159 #6 THHN in 5" Rigid, drawn to scale

This pull in numbers

159 wires fill
39.9 % of 5" Rigid
Limit for three or more
40 %
For 160 or more
6" Rigid, up to 230
Pipe to wire diameter
19.97 to 1
In THW insulation
111 fit
In XHHW-2 insulation
137 fit

Before you pull 159

#6 THHN in other 5" conduit

ConduitInside areaMost #6 THHN
Rigid metal conduit (RMC, GRC)20.212159
Rigid PVC conduit, Schedule 4019.761156
Rigid PVC conduit, Schedule 8017.855141

#6 THHN in other Rigid sizes

Other wire sizes in 5" Rigid

Charts