How many #8 THHN fit in 3-1/2" Liquidtight?
1068 AWG THHN/THWN-2 wires in 3-1/2" Liquidtight flexible metal conduit (LFMC)
9.731 sq in × 40 % = 3.8924 sq in allowed. ÷ 0.0366 sq in per wire = 106.35, so 106.
This pull in numbers
- 106 wires fill
- 39.9 % of 3-1/2" Liquidtight
- Limit for three or more
- 40 %
- For 107 or more
- 4" Liquidtight, up to 138
- Pipe to wire diameter
- 16.30 to 1
- In THW insulation
- 89 fit
- In XHHW-2 insulation
- 89 fit
Before you pull 106
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 106 is the total, not the hots.
- Derating. If all 106 were current-carrying, each would be adjusted to 35 % of its ampacity (Table 310.15(C)(1)): a #8 THHN at 55 A in the 90 °C column becomes 19.3 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#8 THHN in other 3-1/2" conduit
| Conduit | Inside area | Most #8 THHN |
|---|---|---|
| Electrical metallic tubing | 11.545 | 126 |
| Intermediate metal conduit | 10.584 | 115 |
| Rigid metal conduit (RMC, GRC) | 10.010 | 109 |
| Rigid PVC conduit, Schedule 40 | 9.737 | 106 |
| Rigid PVC conduit, Schedule 80 | 8.688 | 95 |
| Flexible metal conduit (FMC, Greenfield) | 9.621 | 105 |
| Liquidtight flexible metal conduit (LFMC) | 9.731 | 106 |
#8 THHN in other Liquidtight sizes
Other wire sizes in 3-1/2" Liquidtight
#10: 184#8: 106#6: 76#4: 47#3: 40#2: 33#1: 25#1/0: 21#2/0: 17#3/0: 14#4/0: 12250 kcmil: 10300 kcmil: 8350 kcmil: 7500 kcmil: 5