ConduitCount

How many #8 THHN fit in 1-1/4" PVC Sch 40?

168 AWG THHN/THWN-2 wires in 1-1/4" Rigid PVC conduit, Schedule 40

1.453 sq in × 40 % = 0.5812 sq in allowed. ÷ 0.0366 sq in per wire = 15.88, which Note 7 rounds up to 16 because the decimal is 0.8 or more.

16 #8 THHN in 1-1/4" PVC Sch 40, drawn to scale

This pull in numbers

16 wires fill
40.3 % of 1-1/4" PVC Sch 40
Limit for three or more
40 %
For 17 or more
1-1/2" PVC Sch 40, up to 21
Pipe to wire diameter
6.30 to 1
In THW insulation
13 fit
In XHHW-2 insulation
13 fit

Before you pull 16

#8 THHN in other 1-1/4" conduit

#8 THHN in other PVC Sch 40 sizes

Other wire sizes in 1-1/4" PVC Sch 40

Charts