ConduitCount

How many #8 THHN fit in 4" Liquidtight?

1388 AWG THHN/THWN-2 wires in 4" Liquidtight flexible metal conduit (LFMC)

12.692 sq in × 40 % = 5.0768 sq in allowed. ÷ 0.0366 sq in per wire = 138.71, so 138.

138 #8 THHN in 4" Liquidtight, drawn to scale

This pull in numbers

138 wires fill
39.8 % of 4" Liquidtight
Limit for three or more
40 %
For 139 or more
no bigger Liquidtight
Pipe to wire diameter
18.61 to 1
In THW insulation
116 fit
In XHHW-2 insulation
116 fit

Before you pull 138

#8 THHN in other 4" conduit

ConduitInside areaMost #8 THHN
Electrical metallic tubing14.753161
Intermediate metal conduit13.631149
Rigid metal conduit (RMC, GRC)12.882140
Rigid PVC conduit, Schedule 4012.554137
Rigid PVC conduit, Schedule 8011.258123
Flexible metal conduit (FMC, Greenfield)12.566137
Liquidtight flexible metal conduit (LFMC)12.692138

#8 THHN in other Liquidtight sizes

Other wire sizes in 4" Liquidtight

Charts