ConduitCount

1-1/2" IMC conduit fill

1-1/2" Intermediate metal conduit has an inside area of 2.225 sq in (1.683 in across). Three or more wires may take 40 % of it: 0.8900 sq in.

One wire, 53 %
1.1793 sq in
Two wires, 31 %
0.6897 sq in
Three or more, 40 %
0.8900 sq in
Nipple, 60 %
1.3350 sq in
Support
Every 10 ft, 3 ft from boxes
Sold in
10 ft sticks
42 #10 THHN, the most it may hold, drawn to scale

How many wires fit in 1-1/2" IMC

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG916464
12 AWG674949
10 AWG423636
8 AWG242020
6 AWG171512
4 AWG11119
3 AWG998
2 AWG776
1 AWG564
1/0 AWG454
2/0 AWG443
3/0 AWG333
4/0 AWG221
250 kcmil111
300 kcmil111
350 kcmil111
400 kcmil111
500 kcmil111
600 kcmil111
700 kcmil111
750 kcmil111
800 kcmil110

Other 1-1/2" conduit

ConduitInside area#14#12#10#8#6
Intermediate metal conduit2.2259167422417
Electrical metallic tubing2.0368461382216
Rigid metal conduit (RMC, GRC)2.0718562392216
Rigid PVC conduit, Schedule 401.9868259372115
Rigid PVC conduit, Schedule 801.7117051321813
Flexible metal conduit (FMC, Greenfield)1.8587656352014
Liquidtight flexible metal conduit (LFMC)1.9818159372115
Electrical nonmetallic tubing (smurf tube)1.9868259372115

About IMC

IMC has a thinner wall than rigid, so it has a little more room inside size for size. Support follows 342.30: within 3 ft of each box, then every 10 ft, or longer on straight runs with threaded couplings. See strap spacing and the fill rules.