ConduitCount

1-1/4" PVC Sch 40 conduit fill

1-1/4" Rigid PVC conduit, Schedule 40 has an inside area of 1.453 sq in (1.360 in across). Three or more wires may take 40 % of it: 0.5812 sq in.

One wire, 53 %
0.7701 sq in
Two wires, 31 %
0.4504 sq in
Three or more, 40 %
0.5812 sq in
Nipple, 60 %
0.8718 sq in
Support
Every 5 ft, 3 ft from boxes
Sold in
10 ft sticks
43 #12 THHN, the most it may hold, drawn to scale

How many wires fit in 1-1/4" PVC Sch 40

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG604242
12 AWG433232
10 AWG272424
8 AWG161313
6 AWG11108
4 AWG776
3 AWG665
2 AWG554
1 AWG333
1/0 AWG332
2/0 AWG221
3/0 AWG111
4/0 AWG111
250 kcmil111
300 kcmil111
350 kcmil111
400 kcmil111
500 kcmil110

Other 1-1/4" conduit

ConduitInside area#14#12#10#8#6
Rigid PVC conduit, Schedule 401.4536043271611
Electrical metallic tubing1.4966145281612
Intermediate metal conduit1.6476849311813
Rigid metal conduit (RMC, GRC)1.5266346291612
Rigid PVC conduit, Schedule 801.237513723139
Flexible metal conduit (FMC, Greenfield)1.2775238241410
Liquidtight flexible metal conduit (LFMC)1.5286346291612
Electrical nonmetallic tubing (smurf tube)1.4536043271611

About PVC Sch 40

Schedule 40 is the standard PVC wall. Support spacing gets wider as the size goes up (Table 352.30), and long runs in the sun need expansion fittings (352.44). See strap spacing and the fill rules.