How many #1/0 THHN fit in 2" Flex?
71/0 AWG THHN/THWN-2 wires in 2" Flexible metal conduit (FMC, Greenfield)
3.269 sq in × 40 % = 1.3076 sq in allowed. ÷ 0.1855 sq in per wire = 7.05, so 7.
This pull in numbers
- 7 wires fill
- 39.7 % of 2" Flex
- Limit for three or more
- 40 %
- For 8 or more
- 2-1/2" Flex, up to 10
- Pipe to wire diameter
- 4.20 to 1
- In THW insulation
- 6 fit
- In XHHW-2 insulation
- 7 fit
Before you pull 7
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 7 is the total, not the hots.
- Derating. If all 7 were current-carrying, each would be adjusted to 70 % of its ampacity (Table 310.15(C)(1)): a #1/0 THHN at 170 A in the 90 °C column becomes 119 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#1/0 THHN in other 2" conduit
| Conduit | Inside area | Most #1/0 THHN |
|---|---|---|
| Electrical metallic tubing | 3.356 | 7 |
| Intermediate metal conduit | 3.630 | 8 |
| Rigid metal conduit (RMC, GRC) | 3.408 | 7 |
| Rigid PVC conduit, Schedule 40 | 3.291 | 7 |
| Rigid PVC conduit, Schedule 80 | 2.874 | 6 |
| Flexible metal conduit (FMC, Greenfield) | 3.269 | 7 |
| Liquidtight flexible metal conduit (LFMC) | 3.246 | 7 |
| Electrical nonmetallic tubing (smurf tube) | 3.291 | 7 |
#1/0 THHN in other Flex sizes
Other wire sizes in 2" Flex
#14: 135#12: 98#10: 62#8: 35#6: 25#4: 16#3: 13#2: 11#1: 8#1/0: 7#2/0: 6#3/0: 5#4/0: 4250 kcmil: 3300 kcmil: 3350 kcmil: 1500 kcmil: 1