ConduitCount

How many #1/0 THHN fit in 2" Flex?

71/0 AWG THHN/THWN-2 wires in 2" Flexible metal conduit (FMC, Greenfield)

3.269 sq in × 40 % = 1.3076 sq in allowed. ÷ 0.1855 sq in per wire = 7.05, so 7.

7 #1/0 THHN in 2" Flex, drawn to scale

This pull in numbers

7 wires fill
39.7 % of 2" Flex
Limit for three or more
40 %
For 8 or more
2-1/2" Flex, up to 10
Pipe to wire diameter
4.20 to 1
In THW insulation
6 fit
In XHHW-2 insulation
7 fit

Before you pull 7

#1/0 THHN in other 2" conduit

#1/0 THHN in other Flex sizes

Other wire sizes in 2" Flex

Charts