ConduitCount

How many #12 THHN fit in 2" Flex?

9812 AWG THHN/THWN-2 wires in 2" Flexible metal conduit (FMC, Greenfield)

3.269 sq in × 40 % = 1.3076 sq in allowed. ÷ 0.0133 sq in per wire = 98.32, so 98.

98 #12 THHN in 2" Flex, drawn to scale

This pull in numbers

98 wires fill
39.9 % of 2" Flex
Limit for three or more
40 %
For 99 or more
2-1/2" Flex, up to 147
Pipe to wire diameter
15.69 to 1
In THW insulation
72 fit
In XHHW-2 insulation
72 fit

Before you pull 98

#12 THHN in other 2" conduit

#12 THHN in other Flex sizes

Other wire sizes in 2" Flex

Charts