ConduitCount

How many #1/0 THHN fit in 3-1/2" Flex?

201/0 AWG THHN/THWN-2 wires in 3-1/2" Flexible metal conduit (FMC, Greenfield)

9.621 sq in × 40 % = 3.8484 sq in allowed. ÷ 0.1855 sq in per wire = 20.75, so 20.

20 #1/0 THHN in 3-1/2" Flex, drawn to scale

This pull in numbers

20 wires fill
38.6 % of 3-1/2" Flex
Limit for three or more
40 %
For 21 or more
4" Flex, up to 27
Pipe to wire diameter
7.20 to 1
In THW insulation
17 fit
In XHHW-2 insulation
21 fit

Before you pull 20

#1/0 THHN in other 3-1/2" conduit

ConduitInside areaMost #1/0 THHN
Electrical metallic tubing11.54525
Intermediate metal conduit10.58423
Rigid metal conduit (RMC, GRC)10.01021
Rigid PVC conduit, Schedule 409.73721
Rigid PVC conduit, Schedule 808.68818
Flexible metal conduit (FMC, Greenfield)9.62120
Liquidtight flexible metal conduit (LFMC)9.73121

#1/0 THHN in other Flex sizes

Other wire sizes in 3-1/2" Flex

Charts