ConduitCount

How many #1/0 THHN fit in 2" PVC Sch 40?

71/0 AWG THHN/THWN-2 wires in 2" Rigid PVC conduit, Schedule 40

3.291 sq in × 40 % = 1.3164 sq in allowed. ÷ 0.1855 sq in per wire = 7.10, so 7.

7 #1/0 THHN in 2" PVC Sch 40, drawn to scale

This pull in numbers

7 wires fill
39.5 % of 2" PVC Sch 40
Limit for three or more
40 %
For 8 or more
2-1/2" PVC Sch 40, up to 10
Pipe to wire diameter
4.21 to 1
In THW insulation
6 fit
In XHHW-2 insulation
7 fit

Before you pull 7

#1/0 THHN in other 2" conduit

#1/0 THHN in other PVC Sch 40 sizes

Other wire sizes in 2" PVC Sch 40

Charts