ConduitCount

How many #10 THHN fit in 2-1/2" Flex?

9310 AWG THHN/THWN-2 wires in 2-1/2" Flexible metal conduit (FMC, Greenfield)

4.909 sq in × 40 % = 1.9636 sq in allowed. ÷ 0.0211 sq in per wire = 93.06, so 93.

93 #10 THHN in 2-1/2" Flex, drawn to scale

This pull in numbers

93 wires fill
40.0 % of 2-1/2" Flex
Limit for three or more
40 %
For 94 or more
3" Flex, up to 134
Pipe to wire diameter
15.24 to 1
In THW insulation
81 fit
In XHHW-2 insulation
81 fit

Before you pull 93

#10 THHN in other 2-1/2" conduit

ConduitInside areaMost #10 THHN
Electrical metallic tubing5.858111
Intermediate metal conduit5.13597
Rigid metal conduit (RMC, GRC)4.86692
Rigid PVC conduit, Schedule 404.69589
Rigid PVC conduit, Schedule 804.11978
Flexible metal conduit (FMC, Greenfield)4.90993
Liquidtight flexible metal conduit (LFMC)4.88192

#10 THHN in other Flex sizes

Other wire sizes in 2-1/2" Flex

Charts